{"product_id":"notifier-nmm-100-10-monitor-module-secure-packaging","title":"NMM-100-10 | Notifier Ten-Input Addressable Monitor Module","description":"\u003ch4\u003eDescription \u003c\/h4\u003e\n\u003cp data-start=\"18\" data-end=\"484\"\u003eThe Notifier NMM-100-10 is a ten-input monitor module designed to interface normally open contact devices with FireWarden series intelligent fire alarm control panels. It provides ten addressable Class B or five Class A initiating device circuits and reports supervised device status (normal, open, or short) to the panel. The NMM-100-10 features panel-controlled LED indicators and rotary address switches for flexible system configuration.\u003c\/p\u003e\n\u003ch3 data-start=\"486\" data-end=\"509\"\u003e\u003cbr\u003e\u003c\/h3\u003e\n\u003cp\u003e \u003c\/p\u003e\n\u003ch4\u003eTechnical Specifications \u003c\/h4\u003e\n\u003ctable\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eCondition\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eNew\/Never Used Surplus\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eBrand\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eNotifier\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eCategory\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eFire Alarm Systems\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePart Number\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eNMM-100-10\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSubcategory\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eAddressable Monitor Modules\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNumber of Inputs\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e10 Class B or 5 Class A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eStandby Current\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e3.5 mA (all addresses used)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eAlarm Current\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e55 mA (all LEDs ON)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMaximum IDC Voltage\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e10.2 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMaximum IDC Current\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e240 μA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMaximum IDC Wiring Resistance\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1500 ohms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMaximum SLC Wiring Resistance\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e40 or 50 ohms (panel dependent)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eWire Gauge\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e12 to 18 AWG\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOperating Temperature (UL)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e32°F to 120°F (0°C to 49°C)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eHumidity (UL)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e10% to 85% non-condensing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eDimensions\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e6.8\" H × 5.8\" W × 1.25\" D\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eShipping Weight\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0.76 lb\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eListings\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eUL S635, FM Approved, CSFM Approved, ULC S635 (A version)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eWeight\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0.76 lb\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003cp\u003e \u003c\/p\u003e\n\u003cp\u003e \u003c\/p\u003e\n\u003ch4\u003eInformation About NMM-100-10\u003c\/h4\u003e\n\u003cp\u003eThe NMM-100-10 is an addressable monitor module used in intelligent fire alarm systems to connect devices such as pull stations, waterflow switches, and security contacts to a FireWarden series control panel. The first module address is selectable from 01 to 90, with the remaining nine addresses automatically assigned sequentially, and up to two unused addresses may be disabled. Each point is independently supervised while sharing a common SLC input and supervisory supply. The module supports both Class A and Class B wiring configurations and includes removable plug-in terminal blocks for simplified installation.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong data-start=\"1085\" data-end=\"1102\"\u003eKey Features:\u003cbr\u003e\u003c\/strong\u003e\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003eTen Addressable Inputs: Supports ten Class B or five Class A initiating device circuits.\u003c\/li\u003e\n\u003cli\u003eSequential Address Assignment: First address set via rotary switches; remaining nine auto-assign sequentially.\u003c\/li\u003e\n\u003cli\u003eSupervised Monitoring: Reports normal, open, and short circuit conditions to the control panel.\u003c\/li\u003e\n\u003cli\u003ePanel-Controlled LED Indicators: Green LEDs per point with blink, latch on, or latch off control.\u003c\/li\u003e\n\u003cli\u003eClass A or Class B Operation: Configurable wiring by removing shunt for Class A.\u003c\/li\u003e\n\u003cli\u003eRemovable Terminal Blocks: Accepts 12–18 AWG wiring for simplified installation and servicing.\u003c\/li\u003e\n\u003cli\u003eFlexible Mounting Options: Compatible with CHS-6 chassis, BB-25 cabinet, and BB-XP cabinet.\u003c\/li\u003e\n\u003cli\u003eAgency Approved: UL Listed (S635), FM Approved, CSFM Approved, ULC Listed (NMM-100-10A).\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003eThe NMM-100-10 delivers the reliability and precision required for multi-point monitoring in intelligent fire alarm systems.\u003c\/p\u003e","brand":"Notifier","offers":[{"title":"Default Title","offer_id":51206177620266,"sku":"NMM-100-10","price":1527.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0800\/0392\/4266\/files\/hon-ba-fire-monitor-multi-module-center.jpg?v=1772558401","url":"https:\/\/iqelectro.com\/products\/notifier-nmm-100-10-monitor-module-secure-packaging","provider":"IQElectro","version":"1.0","type":"link"}