1746-NT8 | Allen-Bradley SLC 500 8-Channel Thermocouple/mV Analog Input Module
1746-NT8 | Allen-Bradley SLC 500 8-Channel Thermocouple/mV Analog Input Module
1746-NT8 | Allen-Bradley SLC 500 8-Channel Thermocouple/mV Analog Input Module
    1746-NT8 | Allen-Bradley SLC 500 8-Channel Thermocouple/mV Analog Input Module
1746-NT8 | Allen-Bradley SLC 500 8-Channel Thermocouple/mV Analog Input Module

1746-NT8 | Allen-Bradley SLC 500 8-Channel Thermocouple/mV Analog Input Module

Part #: 1746-NT8 Manufactured by: Allen-Bradley
Regular price
$689.00
Sale price
$689.00
Regular price
15 in Stock
Condition: New – Open box
Shipping calculated at checkout.
Product Overview
The Allen-Bradley 1746-NT8 is a SLC 500 Thermocouple/mV Analog Input Module. This Thermocouple/mV Analog Input Module has ...  Read more
We accept:
  • American Express
  • Apple Pay
  • Diners Club
  • Discover
  • Google Pay
  • Mastercard
  • PayPal
  • Shop Pay
  • Visa
Contact Us!

Talk to a real expert.

Mon–Sat, 7:00 AM – 8:00 PM (EST)
warranty
IQElectro 2-Year Warranty
Warranty for Product #: 1746-NT8
IQElectro offers a free 2-year warranty on all products. You can trust that every purchase is a reliable investment in the future of your company. Warranty Terms
2-3 Day Free Shipping
Packed Ready to Ship
24/7 Expert Support
Return within 30-Days
IQElectro is Not an authorized distributor for Allen-Bradley
Original Manufacturer's Warranty Not Covered, This Product is SURPLUS.

Product Description P/N: 1746-NT8

Description / Specifications

Description

The Allen-Bradley 1746-NT8 is an 8-channel thermocouple and millivolt analog input module designed for temperature and low-level signal monitoring in SLC 500 systems. The 1746-NT8 supports multiple thermocouple types and mV ranges, using sigma-delta conversion for accurate, noise-resistant measurements. Its wide compatibility with fixed and modular SLC 500 controllers makes it suitable for process monitoring and precision temperature applications.

 

 

Technical Specifications

Condition New/Never Used Surplus
Brand Allen-Bradley
Category Input Module
Part Number 1746-NT8
Subcategory Input Module
Series SLC 500
Module Type Thermocouple/mV Analog Input Module
Number of Inputs 8 channels
Supported Thermocouple Types J, K, T, E, S, R, B, N
mV Input Ranges ±50 mV, ±100 mV
Resolution 16-bit in; 14-bit out
A/D Conversion Method Sigma-delta modulation
Open Circuit Detection Zero, Upscale, Downscale
Update Time 356 ms to 4.05 s
Step Response 60 ms input, 2.5 ms output
Backplane Current (5 VDC) 120 mA
Backplane Current (24 VDC) 70 mA
Backplane Power Consumption 2.28 W max
Overvoltage Protection ±30 VDC; 600 W pulsed (1 ms)
Isolation 12.5 VDC circuit isolation; 500 VDC test
Terminal Block 1746-RT34 with CJC sensors
CJC Accuracy ±1.72 °C
Input Impedance >10 MΩ (device <100 Ω recommended)
Indicators 9 green status LEDs
I/O Chassis Location Any slot except Slot 0
Operating Temperature 0…60 °C
Storage Temperature –40…85 °C
Humidity 5–95% non-condensing
Mounting SLC 500 fixed or modular chassis
Compliance UL & cUL listed

 

 

Information About 1746-NT8

The 1746-NT8 is part of the Allen-Bradley SLC 500 I/O family and provides eight isolated analog input channels designed to accept thermocouple or low-level millivolt signals. It supports multiple TC types—including J, K, T, E, S, R, B, and N—and mV inputs up to ±100 mV, making it adaptable for diverse sensing installations. Using sigma-delta A/D conversion, the module offers high noise immunity, programmable digital filtering, and reliable signal capture even in electrically noisy environments. Designed for flexible installation, the 1746-NT8 may be installed in any modular chassis slot except Slot 0, and includes built-in open-circuit detection, self-calibration, and diagnostic indicators for dependable performance.

Key Features

  • 8-Analog Input Channels: Supports thermocouple and millivolt signal types across multiple ranges.
  • Wide Thermocouple Compatibility: Accepts J, K, T, E, S, R, B, and N sensor types.
  • High-Resolution Conversion: Provides 16-bit input resolution and 14-bit output data formatting.
  • Sigma-Delta A/D Technology: Ensures high accuracy with strong rejection of 50–60 Hz noise.
  • Built-In Diagnostics: Includes open-circuit detection, over/under-range alarms, and error bits.
  • Automatic Calibration: Performs periodic self-calibration to maintain measurement accuracy.
  • Flexible Mounting Options: Works with fixed SLC systems or any modular chassis slot except Slot 0.
  • Robust Environmental Ratings: Operates across industrial temperature ranges with 500 V isolation and CJC support.

The 1746-NT8 delivers the reliability and precision required for advanced temperature monitoring and millivolt signal acquisition in industrial control systems.

Frequently Asked Questions about 1746-NT8
Question: What controllers are compatible with the 1746-NT8 module?
Date Update:06/06/2025
Answer:

The 1746-NT8 module is compatible with various SLC 500 processors, making it suitable for different system architectures.

  • SLC 5/01, 5/02, 5/03, 5/04, and 5/05 controllers: These controllers can interface with the 1746-NT8 for thermocouple and mV signal acquisition.
  • Fixed and modular style SLC 500 hardware: The module can be installed in both hardware types for flexible integration.
  • Chassis slot compatibility: Can be installed in any slot except slot 0, which is reserved for the controller or communication modules.
  • Backplane current compatibility: Draws 120mA at 5V DC and 70mA at 24V DC from the I/O chassis backplane.
  • Terminal compatibility: Uses the 1746-RT34 (RTB) removable terminal block for secure field wiring.

These compatibilities ensure that the 1746-NT8 integrates seamlessly with various SLC 500 systems, providing reliable analog input capabilities.

Question: What is the function of the 1746-NT8 module?
Date Update:06/06/2025
Answer:

The 1746-NT8 module is a thermocouple and millivolt analog input module used in SLC 500 automation systems. Its primary function is to convert analog signals from thermocouples (such as J, K, T, E, S, R, B, and N types) or millivolt sources into digital data. This digital data can then be processed by the SLC 500 controller for monitoring, recording, or control purposes. With its 16-bit input resolution and Sigma-Delta A/D conversion, it ensures accurate and stable measurements.

Question: Can the 1746-NT8 module be used with both fixed and modular SLC 500 systems?
Date Update:06/06/2025
Answer:

Yes, the module is compatible with both fixed style and modular style SLC 500 systems. This flexibility allows it to be installed in a wide range of industrial applications. Users should ensure proper slot installation and avoid slot 0, which is reserved for the processor.

Question: How many input channels does the 1746-NT8 module have and how are they configured?
Date Update:06/06/2025
Answer:

The module provides eight input channels, each configurable for thermocouple or millivolt inputs. It supports high-impedance signal acquisition, with an input impedance greater than 10M Ohms, ensuring accurate measurements. The module offers per-channel diagnostics, including open-circuit detection, under-range, and over-range error detection. It uses programmable open-circuit detection that allows upscale, downscale, or zero settings.

Question: Is the 1746-NT8 still in production?
Date Update:06/06/2025
Answer:

No, the 1746-NT8 module is no longer in production. Rockwell Automation has officially discontinued it and recommends planning for migration to newer platforms. However, spare parts or surplus stock may still be available through authorized distributors. Users should consider modern analog input modules for SLC 500 or CompactLogix systems to ensure continued support and future expandability.

IQElectro is not an authorized distributor.
IQElectro LLC (IQElectro) is NOT an Authorized Distributor or in any way affiliated with Rockwell Automation, Siemens, or any other Manufacturers. IQElectro is NOT an Authorized Dealer of this product. The product may be of older version, date codes, or design than that available from authorized dealers. As IQElectro is not an authorized dealer of this product, the Original Manufacturer's Warranty and Support DO NOT apply. IQElectro sells SURPLUS only and DOES NOT SELL SOFTWARE or FIRMWARE licenses For more detailed information, please refer to the full version of our disclaimer policy Disclaimer Policy.
Description / Specifications

Description

The Allen-Bradley 1746-NT8 is an 8-channel thermocouple and millivolt analog input module designed for temperature and low-level signal monitoring in SLC 500 systems. The 1746-NT8 supports multiple thermocouple types and mV ranges, using sigma-delta conversion for accurate, noise-resistant measurements. Its wide compatibility with fixed and modular SLC 500 controllers makes it suitable for process monitoring and precision temperature applications.

 

 

Technical Specifications

Condition New/Never Used Surplus
Brand Allen-Bradley
Category Input Module
Part Number 1746-NT8
Subcategory Input Module
Series SLC 500
Module Type Thermocouple/mV Analog Input Module
Number of Inputs 8 channels
Supported Thermocouple Types J, K, T, E, S, R, B, N
mV Input Ranges ±50 mV, ±100 mV
Resolution 16-bit in; 14-bit out
A/D Conversion Method Sigma-delta modulation
Open Circuit Detection Zero, Upscale, Downscale
Update Time 356 ms to 4.05 s
Step Response 60 ms input, 2.5 ms output
Backplane Current (5 VDC) 120 mA
Backplane Current (24 VDC) 70 mA
Backplane Power Consumption 2.28 W max
Overvoltage Protection ±30 VDC; 600 W pulsed (1 ms)
Isolation 12.5 VDC circuit isolation; 500 VDC test
Terminal Block 1746-RT34 with CJC sensors
CJC Accuracy ±1.72 °C
Input Impedance >10 MΩ (device <100 Ω recommended)
Indicators 9 green status LEDs
I/O Chassis Location Any slot except Slot 0
Operating Temperature 0…60 °C
Storage Temperature –40…85 °C
Humidity 5–95% non-condensing
Mounting SLC 500 fixed or modular chassis
Compliance UL & cUL listed

 

 

Information About 1746-NT8

The 1746-NT8 is part of the Allen-Bradley SLC 500 I/O family and provides eight isolated analog input channels designed to accept thermocouple or low-level millivolt signals. It supports multiple TC types—including J, K, T, E, S, R, B, and N—and mV inputs up to ±100 mV, making it adaptable for diverse sensing installations. Using sigma-delta A/D conversion, the module offers high noise immunity, programmable digital filtering, and reliable signal capture even in electrically noisy environments. Designed for flexible installation, the 1746-NT8 may be installed in any modular chassis slot except Slot 0, and includes built-in open-circuit detection, self-calibration, and diagnostic indicators for dependable performance.

Key Features

  • 8-Analog Input Channels: Supports thermocouple and millivolt signal types across multiple ranges.
  • Wide Thermocouple Compatibility: Accepts J, K, T, E, S, R, B, and N sensor types.
  • High-Resolution Conversion: Provides 16-bit input resolution and 14-bit output data formatting.
  • Sigma-Delta A/D Technology: Ensures high accuracy with strong rejection of 50–60 Hz noise.
  • Built-In Diagnostics: Includes open-circuit detection, over/under-range alarms, and error bits.
  • Automatic Calibration: Performs periodic self-calibration to maintain measurement accuracy.
  • Flexible Mounting Options: Works with fixed SLC systems or any modular chassis slot except Slot 0.
  • Robust Environmental Ratings: Operates across industrial temperature ranges with 500 V isolation and CJC support.

The 1746-NT8 delivers the reliability and precision required for advanced temperature monitoring and millivolt signal acquisition in industrial control systems.