Part #: 1756-L63 Manufactured by: Allen-Bradley
Regular price
$4,468.00
Sale price
$4,468.00
Regular price
4 in Stock
Condition: New-Surplus Original Box
Shipping calculated at checkout.
Product Overview
Allen Bradley ControlLogix Processor Module with 2, 4, or 8 MB Fixed Memory and See Compact Flash Card 1784-CF64 Nonvolati...  Read more
We accept:
  • American Express
  • Apple Pay
  • Diners Club
  • Discover
  • Google Pay
  • Mastercard
  • PayPal
  • Shop Pay
  • Venmo
  • Visa
warranty
IQElectro 2-Year Warranty
Warranty for Product #: 1756-L63
IQElectro offers a free 2-year warranty on all products. You can trust that every purchase is a reliable investment in the future of your company. Warranty Terms
2-3 Day Free Shipping
Packed Ready to Ship
24/7 Expert Support
Return within 30-Days
IQElectro LLC BBB Business Review
IQElectro is Not an authorized distributor for Allen-Bradley
Original Manufacturer's Warranty Not Covered, This Product is SURPLUS.

Product Description P/N: 1756-L63

Description / Specifications

Description 

The Allen-Bradley 1756-L63 is a 5560 ControlLogix Programmable Automation Controller (PAC). This controller features 8 MB user memory and I/O memory of 478 KB. It has 1 RS232 Serial port and supports interfacing of up to 128,000 Discrete I/O and 4000 Analog I/O memory.

 

Technical Specifications 

 

Brand Allen-Bradley
Series ControlLogix
Part Number 1756-L63
Manufacturer Rockwell Automation
Optional Communication adapters • EtherNet/IP • ControlNet • DeviceNet • Data Highway Plus • Remote I/O • SynchLink • Third-party process and device networks
No. of task 32
Non-volatile memory 128 MB (optional)
User Memory 8 MB
I/O Memory 478 KB
Product Type Programmable Automation Controller
Programs per task 100 Programs
Event Task All Triggers
Built-in communication 1 USB port
Module Type Processor Module
Maximum I-O 128000
Maximum Analog I-O 4000
Redundancy Full Support
Fixed Memory 2, 4, or 8 MB
Nonvolatile Memory See Compact Flash Card 1784-CF64
Program Scan Time 0.08 milliseconds
Backplane Current (5Volts DC) 1.2 Amps
Backplane Current (24 Volts DC) 14 milliamps
Vibration 10 to 500 Hertz
Relative Humidity 5 to 95%
Battery 1756-BA1 or 1756-BATM

  

 

Information About 1756-L63

The 1756-L63 is a Programmable Automation Controller (PAC) from Allen-Bradley. This controller is part of the earlier Logix controller version which is specifically part of the 5560 product series. This controller comes with an RS232 Serial communication interface as the primary communication port, however, this controller supports other communication protocols such as EtherNet/IP, ControlNet, DeviceNet, Data Highway Plus, Remote I/O, SynchLink and other 3rd party communication protols by installing Allen-Bradley communication adapters and encompass partner modules.

The 1756-L63 is a Chassis based controller. It is installed a variety of ControlLogix chassis such as 1756-A4, 1756-A7, 1756-A10, 1756-A13, and 1756-A17. It is also compatible for use with standard and redundant power supplies such as 1756-PA50, 1756-PA72, 1756-PA75, 1756-PB50, 1756-PB72, 1756-PB75 or 1756-PA75R, 1756-PB75R, 1756-PSCA2, respectively. It supports implementation of controller redundancy as well as integrated motion using Serial Real-Time Communication System (SERCOS), Analog options via encoder input, LDT input, SSI input and motion over Ethernet I/P network.

This controller comes with 8 MB user memory and I/O memory of 478 KB. It may be added with non-volatile memory storage via the 1784-CF128 only which has 128 MB memory size. For I/O interfacing, this controller supports up to 128,000 Discrete Input and Output and 4000 Analog Input and Output signals. It uses battery backed-up Random Access Memory (RAM) with battery part numbers of 1756-BA1, 1756-BATM, 1756-BATA for Series A controllers and 1756-BA2 Series B controllers.

The 1756-L63 controller has a built-in RS-132 serial communication port. The communication options available for this controller include the DeviceNet, ControlNet, EtherNet/IP, SynchLink, Remote I/O, Data Highway Plus, and third-party process and device networks. Serial port communications modules that this controller supports are the Modbus via logic, DH-485, DF1 radio modem, ASCII, and the DF1 full/half-duplex modules. The continuous isolation voltage of the 1756-L63 controller is 30 Volts and it has a basic insulation type. It has also been type-tested at 720 Volts DC for 60 seconds. It has a power dissipation of 3.5 W and a thermal dissipation of 11.9 BTU/hour. Its current draw at 5.1 Volts DC is 1200 mA and its current draw at 24 Volts DC is 14 mA. It has a vibration of 2 g at 10 to 500 Hertz. The 1756-L63 controller has an operating shock of 30 g and a non-operating shock of 50 g. It also has an operating temperature range of 0 to 60 degrees Celsius and a non-operating temperature range of -40 to 85 degrees Celsius. It also has a maximum surrounding air temperature of 60 degrees Celsius.



Manufacturer information

Allen-Bradley, a brand of Rockwell Automation, specializes in manufacturing industrial automation equipment. The product range includes programmable logic controllers (PLCs), motion control systems, safety devices, motor control equipment, automation software, and HMI panels. Allen-Bradley products are known for their reliability and integration with other systems.

Frequently Asked Questions about 1756-L63
Question: What is the 1756-L63?
Date Update:06/06/2025
Answer:

The 1756-L63 is a ControlLogix processor module (part of the Allen-Bradley ControlLogix family) used in large and complex automation systems.

Key specs include:

  • Memory: 8 MB
  • Communication: Multiple backplane communication channels
  • Redundancy capable for high-availability applications
  • Battery-backed RAM for data retention
Question: How do I wire the 1756-L63 processor?
Date Update:06/06/2025
Answer:
  • The processor itself plugs into a ControlLogix chassis (1756-A4, A7, A10, A13) and does not have field wiring directly.
  • Communication wiring (Ethernet, ControlNet, DeviceNet, etc.) is handled via communication modules (like 1756-ENBT for Ethernet).
  • The battery module (1756-BA2) and energy storage module (1756-ESMCAP) are connected directly to the 1756-L63.
Question: How do I program the 1756-L63?
Date Update:06/06/2025
Answer:
  • Use RSLogix 5000 or Studio 5000 Logix Designer software for programming.
  • Develop your ladder logic, function block, structured text, or SFC applications.
  • Download the program via:
    Ethernet (using 1756-ENBT or EN2T modules)
    Serial (RS-232) via the mini-DIN connector on the processor (requires the 1756-CP3 cable)
Question: How do I set up communication?
Date Update:06/06/2025
Answer:
  • Add communication modules (like 1756-ENBT for Ethernet) to the chassis.
  • In Studio 5000, configure the modules (IP address, drivers).
  • Create controller tags for I/O and communication with other devices.
Question: Can I use the 1756-L63 in a redundant system?
Date Update:06/06/2025
Answer:

Yes. The 1756-L63 supports redundancy for critical applications. Use Rockwell Automation’s redundancy configuration tools and guidelines in the redundancy user manual.

IQElectro is not an authorized distributor.
QElectro LLC (IQElectro) is NOT an Authorized Distributor or in any way affiliated with Rockwell Automation, Siemens, or any other Manufacturers. IQElectro is NOT an Authorized Dealer of this product. The product may be of older version, date codes, or design than that available from authorized dealers. As IQElectro is not an authorized dealer of this product, the Original Manufacturer's Warranty and Support DO NOT apply. IQElectro sells SURPLUS only and DOES NOT SELL SOFTWARE or FIRMWARE licenses For more detailed information, please refer to the full version of our disclaimer policy Disclaimer Policy.
Description / Specifications

Description 

The Allen-Bradley 1756-L63 is a 5560 ControlLogix Programmable Automation Controller (PAC). This controller features 8 MB user memory and I/O memory of 478 KB. It has 1 RS232 Serial port and supports interfacing of up to 128,000 Discrete I/O and 4000 Analog I/O memory.

 

Technical Specifications 

 

Brand Allen-Bradley
Series ControlLogix
Part Number 1756-L63
Manufacturer Rockwell Automation
Optional Communication adapters • EtherNet/IP • ControlNet • DeviceNet • Data Highway Plus • Remote I/O • SynchLink • Third-party process and device networks
No. of task 32
Non-volatile memory 128 MB (optional)
User Memory 8 MB
I/O Memory 478 KB
Product Type Programmable Automation Controller
Programs per task 100 Programs
Event Task All Triggers
Built-in communication 1 USB port
Module Type Processor Module
Maximum I-O 128000
Maximum Analog I-O 4000
Redundancy Full Support
Fixed Memory 2, 4, or 8 MB
Nonvolatile Memory See Compact Flash Card 1784-CF64
Program Scan Time 0.08 milliseconds
Backplane Current (5Volts DC) 1.2 Amps
Backplane Current (24 Volts DC) 14 milliamps
Vibration 10 to 500 Hertz
Relative Humidity 5 to 95%
Battery 1756-BA1 or 1756-BATM

  

 

Information About 1756-L63

The 1756-L63 is a Programmable Automation Controller (PAC) from Allen-Bradley. This controller is part of the earlier Logix controller version which is specifically part of the 5560 product series. This controller comes with an RS232 Serial communication interface as the primary communication port, however, this controller supports other communication protocols such as EtherNet/IP, ControlNet, DeviceNet, Data Highway Plus, Remote I/O, SynchLink and other 3rd party communication protols by installing Allen-Bradley communication adapters and encompass partner modules.

The 1756-L63 is a Chassis based controller. It is installed a variety of ControlLogix chassis such as 1756-A4, 1756-A7, 1756-A10, 1756-A13, and 1756-A17. It is also compatible for use with standard and redundant power supplies such as 1756-PA50, 1756-PA72, 1756-PA75, 1756-PB50, 1756-PB72, 1756-PB75 or 1756-PA75R, 1756-PB75R, 1756-PSCA2, respectively. It supports implementation of controller redundancy as well as integrated motion using Serial Real-Time Communication System (SERCOS), Analog options via encoder input, LDT input, SSI input and motion over Ethernet I/P network.

This controller comes with 8 MB user memory and I/O memory of 478 KB. It may be added with non-volatile memory storage via the 1784-CF128 only which has 128 MB memory size. For I/O interfacing, this controller supports up to 128,000 Discrete Input and Output and 4000 Analog Input and Output signals. It uses battery backed-up Random Access Memory (RAM) with battery part numbers of 1756-BA1, 1756-BATM, 1756-BATA for Series A controllers and 1756-BA2 Series B controllers.

The 1756-L63 controller has a built-in RS-132 serial communication port. The communication options available for this controller include the DeviceNet, ControlNet, EtherNet/IP, SynchLink, Remote I/O, Data Highway Plus, and third-party process and device networks. Serial port communications modules that this controller supports are the Modbus via logic, DH-485, DF1 radio modem, ASCII, and the DF1 full/half-duplex modules. The continuous isolation voltage of the 1756-L63 controller is 30 Volts and it has a basic insulation type. It has also been type-tested at 720 Volts DC for 60 seconds. It has a power dissipation of 3.5 W and a thermal dissipation of 11.9 BTU/hour. Its current draw at 5.1 Volts DC is 1200 mA and its current draw at 24 Volts DC is 14 mA. It has a vibration of 2 g at 10 to 500 Hertz. The 1756-L63 controller has an operating shock of 30 g and a non-operating shock of 50 g. It also has an operating temperature range of 0 to 60 degrees Celsius and a non-operating temperature range of -40 to 85 degrees Celsius. It also has a maximum surrounding air temperature of 60 degrees Celsius.



Manufacturer information

Allen-Bradley, a brand of Rockwell Automation, specializes in manufacturing industrial automation equipment. The product range includes programmable logic controllers (PLCs), motion control systems, safety devices, motor control equipment, automation software, and HMI panels. Allen-Bradley products are known for their reliability and integration with other systems.

Check Out These Related Products