Marvair S/04581 CommStat 3 Lead/Lag HVAC Controller for Dual Air Conditioners
- Regular price
- $2,299.00
- Sale price
- $2,299.00
- Regular price
-
Couldn't load pickup availability
Product Description P/N: S/04581
Description
The Marvair S/04581 CommStat 3 is a solid-state lead/lag HVAC controller designed to manage two compatible single-stage air conditioners. It balances equipment operation through automatic lead rotation and allows the second unit to assist when additional cooling is required.
Technical Specifications
| Condition | New/Never Used Surplus |
| Brand | Marvair |
| Category | HVAC |
| Part Number | S/04581 |
| Subcategory | HVAC Controller |
| Series | CommStat 3 |
| Controller Type | Solid-state lead/lag |
| Controlled Equipment | Two compatible single-stage air conditioners |
| Primary Supply Voltage | 24 VAC |
| Backup Supply Input | External 24 or 48 VDC |
| Lead/Lag Changeover Interval | 0.5–7 days in 0.5-day increments |
| Factory Changeover Setting | 7 days |
| Cooling Setpoint Range | 65–95 °F |
| Heating Setpoint Range | 50–80 °F |
| Temperature Display | Digital, °F/°C selectable |
| Temperature Sensor | Built-in |
| Alarm Outputs | Dry contacts, NO/NC connections |
| Anti-Short-Cycle Delay | Adjustable, 1–10 minutes; disabled by default |
| Enclosure Material | Polycarbonate |
| Mounting | Wall |
| Weight | 1.40 lbs |
Information About S/04581
The S/04581 is a programmable HVAC controller for telecommunications shelters and equipment enclosures. It operates from 24 VAC and accepts an external 24 or 48 VDC backup supply for its display, interface, and alarm functions. A built-in temperature sensor, digital display, and status LEDs support local monitoring. Programmable changeover intervals and alarm relay outputs help coordinate redundant cooling equipment.
Key Features:
- Dual-unit control: Manages two compatible single-stage air conditioners.
- Lead/lag rotation: Provides programmable changeover intervals from 0.5 to 7 days.
- Additional cooling: Allows the lag unit to assist during increased demand.
- Temperature monitoring: Includes a built-in sensor and digital temperature display.
- Status indication: Uses LEDs to identify power, operating mode, and lead unit.
- Alarm contacts: Provides dry relay outputs for remote notification.
- Program retention: Preserves configured settings during power loss.
- Anti-short-cycle function: Offers an adjustable compressor restart delay.
The S/04581 delivers the reliability and precision required for redundant air conditioning control in telecommunications facilities.
Description
The Marvair S/04581 CommStat 3 is a solid-state lead/lag HVAC controller designed to manage two compatible single-stage air conditioners. It balances equipment operation through automatic lead rotation and allows the second unit to assist when additional cooling is required.
Technical Specifications
| Condition | New/Never Used Surplus |
| Brand | Marvair |
| Category | HVAC |
| Part Number | S/04581 |
| Subcategory | HVAC Controller |
| Series | CommStat 3 |
| Controller Type | Solid-state lead/lag |
| Controlled Equipment | Two compatible single-stage air conditioners |
| Primary Supply Voltage | 24 VAC |
| Backup Supply Input | External 24 or 48 VDC |
| Lead/Lag Changeover Interval | 0.5–7 days in 0.5-day increments |
| Factory Changeover Setting | 7 days |
| Cooling Setpoint Range | 65–95 °F |
| Heating Setpoint Range | 50–80 °F |
| Temperature Display | Digital, °F/°C selectable |
| Temperature Sensor | Built-in |
| Alarm Outputs | Dry contacts, NO/NC connections |
| Anti-Short-Cycle Delay | Adjustable, 1–10 minutes; disabled by default |
| Enclosure Material | Polycarbonate |
| Mounting | Wall |
| Weight | 1.40 lbs |
Information About S/04581
The S/04581 is a programmable HVAC controller for telecommunications shelters and equipment enclosures. It operates from 24 VAC and accepts an external 24 or 48 VDC backup supply for its display, interface, and alarm functions. A built-in temperature sensor, digital display, and status LEDs support local monitoring. Programmable changeover intervals and alarm relay outputs help coordinate redundant cooling equipment.
Key Features:
- Dual-unit control: Manages two compatible single-stage air conditioners.
- Lead/lag rotation: Provides programmable changeover intervals from 0.5 to 7 days.
- Additional cooling: Allows the lag unit to assist during increased demand.
- Temperature monitoring: Includes a built-in sensor and digital temperature display.
- Status indication: Uses LEDs to identify power, operating mode, and lead unit.
- Alarm contacts: Provides dry relay outputs for remote notification.
- Program retention: Preserves configured settings during power loss.
- Anti-short-cycle function: Offers an adjustable compressor restart delay.
The S/04581 delivers the reliability and precision required for redundant air conditioning control in telecommunications facilities.