Most contactor problems I get called out for aren't contactor problems. Somebody followed a contactor wiring diagram, checked it twice, and the thing sits there dead, drops out the second Start is released, or won't let go on Stop. The drawing was usually fine. What got skipped was reading the part: which two screws are the coil, what voltage and current type it wants, and whether this contactor's aux contact is even normally open.
So that's the order here: terminals, the control circuit that holds the coil in, the coil, and what I measure when a correctly wired contactor still misbehaves.
Every number on the contactor means something
A diagram only helps if you can find each terminal it names on the real device. The numbering is close to universal on IEC-style contactors and overload relays, and less random than it looks.
|
Marking |
What it is |
What lands on it |
|
1/L1, 3/L2, 5/L3 |
Main poles, line side |
Supply from the fuses or breaker |
|
2/T1, 4/T2, 6/T3 |
Main poles, load side |
The overload relay, then the motor |
|
A1, A2 |
Coil |
Control voltage. On a polarized DC coil A1 is positive |
|
13-14 |
Auxiliary contact, normally open |
Seal-in across Start, or a run signal |
|
21-22 |
Auxiliary contact, normally closed |
Interlock on a reversing pair, a "stopped" lamp |
|
95-96 |
Overload relay contact, normally closed |
In series with the coil |
|
97-98 |
Overload relay contact, normally open |
Trip lamp or PLC input |
Terminal markings on a contactor wiring diagram and on the part itself
On the aux contacts, the second digit is the one that matters: 1-2 means normally closed, 3-4 normally open. The first digit just counts. 13-14 is the first contact, 21-22 the second, and an add-on block carries on with 31-32, 43-44 and so on.
Don't wire by position. On a TeSys D the coil terminals sit right next to 13-14 and 21-22, close enough that a coil wire lands on an aux screw more often than anyone admits. An Allen-Bradley 100-C ships with A1 and A2 on the line side, and a U in the catalog number moves them to the load side, so a 100-C09UEJ10 has its coil at the bottom. Same frame, coil on the opposite end.
The catalog number tells you the aux contact too. On a 100-C09 the last two digits are the built-in contact: 10 is one normally open, 01 is one normally closed. That comes back in a minute.

What a 100-C catalog number tells you before you follow any contactor wiring diagram: frame, coil terminal position, coil code and the built-in aux contact.
The power side: line in at the top, motor out at the bottom
The power half of a contactor wiring diagram is the easy half. L1, L2 and L3 come off the branch protection onto 1, 3 and 5. Terminals 2, 4 and 6 feed the overload relay, and the overload relay feeds the motor.
Single-phase on a 3-pole contactor is where people improvise. The standard single-phase starter drawing takes the first leg through pole 1 and runs the second through pole 3, back up into pole 5 and out through 6, so all three overload elements carry motor current. Copy the loop, don't leave a pole empty.
Most melted contactor wires I've pulled out of panels weren't overcurrent. They were loose screws. A 100-C09 wants 1.5 to 2.0 N·m (13.3 to 17.7 lb-in) on the main terminals and only 1 to 1.5 N·m (9 to 13 lb-in) on its coil terminals. A TeSys D LC1D09 takes 1.7 N·m on power and control alike. Insulation trapped under the clamp plate, or strands squeezed out beside it, feels tight and still runs hot. I ferrule every stranded control wire and tug each one after tightening.

A complete contactor wiring diagram for a 3-phase motor with 120 V AC control: power on the left, the control rung on the right, the 13-14 seal-in branch in orange.
The control circuit: why the coil stays on after you let go of Start
This is the part of a contactor wiring diagram people actually get stuck on, and it's one rung. On a 120 V AC control circuit, follow it from the hot side:
1. X1 through the control fuse.
2. Through the overload relay's 95-96, closed unless the relay has tripped.
3. Through Stop, a normally closed button.
4. Through Start, a normally open button, with the contactor's own 13-14 wired in parallel across it.
5. Into A1, out of A2, back to X2.
Press Start and current reaches A1 through the button. The contactor pulls in and 13-14 closes with the main poles, so now there are two paths around Start. Let go, and the second path, through the contactor's own contact, keeps the coil fed. That's the seal-in, or holding contact. It holds until something in series opens: Stop, 95-96, the fuse, or the supply.
Where 13 lands decides whether Stop works. It goes on the junction between Stop and Start. Land it on the line side of Stop and the seal-in goes around Stop: once the motor runs, only a trip, a blown fuse or the disconnect will drop it.

The same rung as the contactor wiring diagram above, stripped down to the seal-in.
Say you swap a 100-C0910 for a 100-C0901 because that's what was on the shelf. Same frame, same coil code. Wire it to the same contactor wiring diagram and it pulls in while Start is held, then drops the instant you let go. A 01 has no normally open contact at all. Fit a normally open aux block or use the right part.
2-wire or 3-wire control
What I just walked through is 3-wire control: momentary buttons, and the contactor remembers. 2-wire control skips the seal-in. A maintained contact sits in series with the coil and holds it on for as long as that contact stays closed.
|
|
2-wire |
3-wire |
|
Pilot device |
Maintained contact: selector switch, float, pressure switch |
Momentary Start and Stop buttons |
|
What keeps the coil in |
The pilot contact itself |
The contactor's 13-14 across Start |
|
After a power dip |
Restarts by itself if the contact is still closed |
Stays off until someone presses Start |
|
Wires from pilot device to starter |
2 |
3 |
|
Where I use it |
A pump on a float, anything that has to come back on its own |
Pretty much any machine with an operator |
2-wire vs 3-wire control in a contactor wiring diagram
That restart behavior is the reason to pick one over the other. Pair 2-wire control with an overload relay on automatic reset and the motor comes back by itself after a trip, with nobody there. Not on anything that can catch a hand.
Where 95-96 goes, and the rest of the rung
The IEC starter drawings I work from most put 95-96 first, right after the control fuse. Older NEMA-style prints park it between the coil and the return. Electrically it only has to be in series with the coil; the drawing side of that I covered in the article on the overload relay symbol.
An emergency stop goes in series too, ahead of the overload contact. On a reversing pair each coil runs through the other contactor's normally closed 21-22, plus a mechanical interlock, so forward can't energize while reverse is in. Each direction has its own 13-14 seal-in.
When a PLC output drives the coil, the seal-in usually lives in the program, and the real question is whether the output survives the coil. That one has its own interposing relay article.
The coil: voltage, AC or DC, then which end is plus
The coil voltage in a contactor wiring diagram is whatever feeds the control circuit. A 480 V motor with a 120 V control transformer gets a 120 V coil; on a common-control starter the coil runs straight off the line, so it's line voltage.
On a 100-C09 the coil code sits between the frame size and the aux digits. D is 120 V 60 Hz, KJ is 24 V AC 50/60 Hz, EJ is 24 V DC with an electronic coil. A 100-C09KJ10 and a 100-C09EJ10 are both 24 V coils on the same frame. One wants AC, the other DC. Order by the code, not by the voltage.
DC adds polarity, sometimes. A TeSys D with a DC coil wants positive on A1; its built-in suppressor makes it polarity sensitive. ABB's low-consumption AF..Z want A1+ and A2- only with 12-20 V or 24 V DC coils. No blanket rule, then. If the coil is marked + and -, follow the marks.
|
Contactor |
Coil |
Pick-up range |
Drops out at |
Suppressor, polarity |
|
100-C09D10 |
120 V AC, 60 Hz |
102-132 V (0.85-1.1 x Us) |
36-72 V (0.3-0.6 x Us) |
Plain AC coil, no polarity |
|
100-C09KJ10 |
24 V AC |
20.4-26.4 V (0.85-1.1 x Us) |
7.2-14.4 V (0.3-0.6 x Us) |
Plain AC coil, no polarity |
|
100-C09EJ10 |
24 V DC, electronic |
16.8-30 V (0.7-1.25 x Us) |
7.2-9.6 V (0.3-0.4 x Us) |
Integrated diode |
|
LC1D09B7 |
24 V AC |
19.2-26.4 V at 50 Hz, 20.4-26.4 V at 60 Hz |
7.2-14.4 V (0.3-0.6 x Uc) |
No suppressor, no polarity |
|
LC1D09BL |
24 V DC, low consumption |
19.2-30 V (0.8-1.25 x Uc) |
2.4-7.2 V (0.1-0.3 x Uc) |
Peak-limiting diode, A1 positive |
|
LC1D09BD |
24 V DC, standard |
16.8-30 V (0.7-1.25 x Uc) |
2.4-6 V (0.1-0.25 x Uc) |
Peak-limiting diode, A1 positive |
Pick-up and drop-out on a few common 9 A contactor coils (Us and Uc both mean rated coil voltage; TeSys D figures are at 60 °C)
Look at the last two rows. A 24 V DC TeSys D can stay pulled in with as little as 2.4 V across the coil, depending on the unit. Between drop-out and pick-up a contactor stays where it already is, and that band explains a lot of "won't release" calls. A few volts left on A1 after Stop opens, from a second feed like 13 landed ahead of Stop or another device wired in parallel, can hold a DC coil in.
Then the suppressor. A plain diode across a DC coil keeps current circulating after the supply opens, so the contactor lets go late. On Siemens SIRIUS contactors a freewheel diode stretches the off-delay six to ten times, a diode with a Zener two to six times, a varistor adds only 2 to 5 ms, and an RC module leaves it unchanged. Slow release with a plain diode on the coil is the diode doing its job. Not a sticky armature.
When a correct contactor wiring diagram still won't work
Read the coil label once more before the meter comes out. Then measure voltage, not resistance. Black lead on X2, red lead walking from the fuse toward A1, and the reading drops to 0 V right after the device that's open. An ohmmeter on a contact that's still wired in reads back through the coil and the control transformer, so it can show a value across a contact that's actually open.

Walking a contactor wiring diagram with a meter: hold Start, black lead on X2, red lead from point 1 to point 4.
|
Symptom |
What I measure |
What it usually means |
|
Nothing happens on Start |
Voltage A1 to A2 while Start is held |
0 V: something upstream is open, walk the rung. Full voltage, no movement: open coil, wrong coil, or a jammed armature |
|
Pulls in only while Start is held |
Power locked out, wire lifted off 14, ohms across 13-14 with the armature pushed in by hand |
Open: no normally open contact there. Wrong terminals, a 01 contact, or no aux block |
|
Won't drop out on Stop |
Voltage A1 to A2 with Stop held |
Above drop-out: something else feeds A1, such as 13 landed ahead of Stop. Near 0 V: diode release delay, or stuck or welded contacts |
|
Chatters or buzzes |
AC voltage at A1-A2 the moment the motor starts |
Sags below the operating range: control transformer too small or control run too long |
|
Drops out by itself |
State of 95-96 |
A trip opens 95-96 and closes 97-98. The Stop button on an E100 relay opens 95-96 but leaves 97-98 open, so no trip lamp |
|
Burns coils |
Coil voltage while running, armature seating fully |
Over 1.1 x Us, an AC coil fed DC, or an armature that never closes. A 100-C09 coil takes 75 VA pulling in and 9.5 VA holding, so one that doesn't seat runs hot |
What I check, symptom by symptom
That last row gets chased the longest. People swap coil after coil when the coil is the victim, not the cause.
FAQ
What do A1 and A2 mean on a contactor wiring diagram?
The two ends of the coil. Whatever feeds the control circuit goes across them. On a polarized DC coil A1 is positive.
Does it matter which wire goes to A1 and which to A2?
On an AC coil, no. On a DC coil, only if the terminals are marked + and -, and TeSys D DC coils are: positive on A1. On an unmarked coil I still follow the drawing, so the next person can trace it.
Why does my contactor drop out when I release Start?
No working seal-in. The normally open aux contact isn't across Start, it's landed on 21-22, or the contactor's only built-in contact is normally closed, like on a 100-C0901.
Where does the overload contact go in a contactor wiring diagram?
95-96 goes in series with the coil, anywhere in the rung, as long as opening it drops the coil. 97-98 is a signal contact for a lamp or a PLC input and never stops the motor on its own.
If the contactor itself is the problem
Sometimes it is: a coil cooked by the wrong supply, contacts welded after a short. Match the replacement on frame, coil code and aux digits, not just the amp rating. We keep Allen-Bradley 100-C contactors on the shelf as surplus with a two-year warranty, including the 100-C09D10 with a 120 V coil, the 24 V AC 100-C09KJ10, the 24 V DC 100-C09EJ10 and the load-side-coil 100-C09UEJ10. Send us the number off the old one and we'll match it to the contactor wiring diagram you already have.