PowerFlex 40 parameters list: what to set, what quietly overrides it, and what to copy before the swap

November 20, 2026
Allen-Bradley PowerFlex 40 drive 22B-D010N104 on a workbench, keypad and LED display facing the camera
Published on  Updated on  

Most PowerFlex 40 calls I get now start the same way. The drive is already off the wall, nobody wrote the settings down, and the replacement sits on the bench at factory defaults. Rockwell discontinued the PowerFlex 40 on June 30, 2025, so it only gets more common: a surplus PF40 goes back in, or the machine moves to a PowerFlex 525.

The full PowerFlex 40 parameters list runs past a hundred entries. On a normal machine you set maybe twenty. Here they are, plus the inputs that override them without telling you, and how the numbers line up on a 525. Mostly they don't.

The PowerFlex 40 parameters list for a basic startup: P031 to P043

Everything a PowerFlex 40 needs to turn a motor sits in the Basic Program group, 13 parameters. P is Basic Program, A is Advanced, d is display only.

Parameter

Name

Default

What I look at

P031

Motor NP Volts

Based on drive rating

Nameplate volts

P032

Motor NP Hertz

60 Hz

50 on a European motor

P033

Motor OL Current

Based on drive rating

F7 Motor Overload at 150% of it for 60 s

P034

Minimum Freq

0.0 Hz

Lowest continuous speed

P035

Maximum Freq

60 Hz

Up to 400 Hz

P036

Start Source

0 "Keypad"

1 "3-wire", 2 "2-wire", 3 "2-W Lvl Sens", 4 "2-W Hi Speed", 5 "Comm Port", 6 "Momt FWD/REV"

P037

Stop Mode

0 "Ramp, CF"

1 "Coast, CF". CF means a stop also clears a fault

P038

Speed Reference

0 "Drive Pot" (1 "InternalFreq" on IP66)

2 "0-10V Input", 3 "4-20mA Input", 4 "Preset Freq", 5 "Comm Port"

P039

Accel Time 1

10.0 s

0 to Maximum Freq, not to base speed

P040

Decel Time 1

10.0 s

Maximum Freq down to 0

P041

Reset To Defalts

0 "Ready/Idle"

1 "Factory Rset" wipes everything, F48. Yes, Defalts

P042

Voltage Class

3 "High Voltage"

600 V drives only. 2 "Low Voltage" runs it as 480 V

P043

Motor OL Ret

0 "Disabled"

1 keeps the overload count through a power cycle

The core of the PowerFlex 40 parameters list, with factory defaults from an IP20 drive.

On a drive that came off another machine I check P036 and P038 first. Out of the box a PF40 starts from its keypad and takes speed from its own pot, so the run inputs on 02 and 03 do nothing until P036 changes. People usually figure that part out. The next part they don't.

Why the drive ignores P036 and P038

Those two are only the starting point. Terminals 05 to 08 can take start or speed away from them, and all four ship set up to do it.

Terminal

Parameter

Factory function

What a closed input does

05

A051 [Digital In1 Sel]

4 "Preset Freq"

Speed jumps to A071, 5.0 Hz

06

A052 [Digital In2 Sel]

4 "Preset Freq"

A072, 10.0 Hz, Accel/Decel Time 2 (05 and 06 together: A073, 20.0 Hz)

07

A053 [Digital In3 Sel]

5 "Local"

Keypad takes start, speed and direction

08

A054 [Digital In4 Sel]

11 "Jog Forward"

Jogs at A078, 10.0 Hz, when stopped

The part of the PowerFlex 40 parameters list that overrides P036 and P038: terminals 05 to 08 as shipped.

The drive checks for overrides in a fixed order and the first match wins: jog, Local, Comm Port, the analog override inputs, P038 at 4 or 5, presets, PID. Only when none of that applies do P036 and P038 actually run the drive.

You don't have to guess which one won. d012 [Control Source] shows it live: rightmost digit is the start source in use, the next one the speed source. P038 says 3 and that digit says 4? A preset took over. d014 shows terminals 05 to 08, and on d013 the third digit from the right is terminal 01. At 0 the drive won't start.

Diagram of the PowerFlex 40 start and speed override order, from the jog input down to P036 and P038

The first matching row takes control. The amber rows are already set up that way on a new drive.

Say a conveyor PF40 dies and the replacement goes in on the same wires. Somebody copies P036 = 2 and P038 = 3, and the belt runs fine on its 4-20 mA signal. Then an operator turns the slow-speed selector on terminal 05 and the belt crawls at 5 Hz instead of 25. The old drive had A071 at 25.0. The new one ships at 5.0, and nobody copied the A group.

Terminal 07 is the other trap. If the old drive used 07 for something else and that contact is closed, the new drive sits under keypad control and ignores the terminal start, P036 = 2 or not. With P038 at 5, though, presets no longer win, so a networked drive won't get dragged to 5 Hz by a forgotten contact on 05.

Terminal 01, the ENBL jumper, and the SNK/SRC switch

No parameter fixes a drive that never sees its stop input. Terminal 01 ships jumpered to 11, the internal +24 V, so the keypad can start the drive. A stop button on 01 means that jumper comes out. Pull it in a rewire, put nothing back, and a healthy drive won't start from anything. An open 01 is a coast stop, except with P036 at 1 "3-wire" or 6 "Momt FWD/REV", where it follows P037.

Three settings on a PF40 aren't in the PowerFlex 40 parameters list at all. They're on the control board:

·       The SNK/SRC DIP switch, factory SRC. In SNK the 01 jumper moves to 01-04, or 01 reads open forever.

·       The ENBL jumper. Take it out and 01 becomes a hardware enable: open means coast, whatever P036 and P037 say.

·       The analog output switch, factory 0-10 V. It has to agree with A065 [Analog Out Sel].

PowerFlex 40 control terminal diagram with the 01-11 jumper, ENBL jumper and SNK/SRC switch marked

As it ships: the 01-11 jumper and three board settings that no PowerFlex 40 parameters list will show you.

Photograph all three before you unbolt anything. Right parameters with a wrong switch look a lot like a dead drive.

Comm settings: the RS-485 port and the 22-COMM-E

A PowerFlex 40 that takes start and speed from a network, including one with a 22-COMM-E EtherNet/IP adapter inside, needs P036 and P038 both at 5 "Comm Port". The rest of the comm side of the PowerFlex 40 parameters list lives in the A group:

Parameter

Default

Note

A103 [Comm Data Rate]

3 "9600"

RS-485 port. Cycle power after a change

A104 [Comm Node Addr]

100

1 to 247. Cycle power after a change

A105 [Comm Loss Action]

0 "Fault"

F81 Comm Loss, coast stop. 3 "Continu Last" keeps the last speed

A106 [Comm Loss Time]

5.0 s

How long before A105 acts

A107 [Comm Format]

0 "RTU 8-N-1"

Parity and stop bits. Cycle power after a change

A164 [Comm Write Mode]

0 "Save"

1 "RAM Only" for a PLC that writes parameters often

A101 [Program Lock]

0 "Unlocked"

1 protects parameters against changes

Comm and lock settings in the PowerFlex 40 parameters list.

A164 I'd look at twice. At 0, every parameter write over comms goes to non-volatile memory, which has a limited life. A PLC that keeps rewriting a preset will wear it out and the drive starts to malfunction. On those machines A164 goes to 1.

The 22-COMM-E keeps its own settings in its own memory:

·       It ships waiting for a BOOTP server. For a fixed IP set adapter parameter 02 [BOOTP] to Disabled, then enter the IP in 03-06, mask 07-10, gateway 11-14, and reset with 17 or a power cycle. A reset while it runs the drive can fault the drive.

·       18 [Comm Flt Action] and 19 [Idle Flt Action] cover a dropped network and a PLC in Program. Default is Fault. Hold Last keeps the motor turning, exactly as risky as it sounds.

·       The speed reference is in Hz with an implied decimal: 300 is 30.0 Hz, 400.0 max. And Start only works after the Stop bit has been 0.

Set to a fixed IP, an old 22-COMM-E moved onto the new drive brings that IP along. The drive parameters stay with the dead drive.

Copy the PowerFlex 40 parameters list before the old drive comes out

I'd rather spend ten minutes on photos than an afternoon guessing which way a DIP switch sat. If the old drive still powers up:

1.    Photograph the nameplate and the control wiring, terminal by terminal.

2.    Cover open: photograph the SNK/SRC switch, ENBL jumper, analog output switch and the 01 jumper.

3.    Note the firmware from d016 [Control SW Ver].

4.    Copy the parameters. A 22-HIM-A3 handheld or 22-HIM-C2S panel HIM on the RJ45 DSI port does CopyCat: Device -> HIM saves a set, up to five, Device <- HIM loads it into the new drive. Or pull the file to a laptop through a 1203-USB with Connected Components Workbench (Standard Edition is free) or DriveExecutive.

5.    Nothing to copy with? Write the PowerFlex 40 parameters list down by hand: the tables here, plus A067/A068 [Accel/Decel Time 2], presets A070 to A077, A055 and A065.

6.    On the replacement, check A101 first. At 1 the parameters are locked.

7.    Starting clean? P041 = 1, clear F48, key in your list.

Allen-Bradley 22-HIM-A3 handheld HIM that copies the PowerFlex 40 parameters list between drives

22-HIM-A3 handheld: CopyCat copies the PowerFlex 40 parameters list from the old drive to the new one.

Moving to a PowerFlex 525: same numbers, different parameters

Picking the hardware is the easy part. A 22B-D010N104 is replaced by the 25B-D010N104: 480 V, 5 HP, 10.5 A, Frame B. The parameters are where people get hurt. P031 to P033 mean the same on both drives. From P034 on the same number is something else, and keying a PowerFlex 40 parameters list into a 525 by number puts your values in the wrong places. The drive has no way of knowing.

PF40

PF40 name

Same number on a 525

Where it lives on a 525

P031

Motor NP Volts

Motor NP Volts

P031

P032

Motor NP Hertz

Motor NP Hertz

P032

P033

Motor OL Current

Motor OL Current

P033

A126

Motor NP FLA

(no such number)

P034

P034

Minimum Freq

Motor NP FLA

P043

P035

Maximum Freq

Motor NP Poles

P044

P036

Start Source

Motor NP RPM

P046, different option numbers

P037

Stop Mode

Motor NP Power

P045

P038

Speed Reference

Voltage Class

P047, different option numbers

P039

Accel Time 1

Torque Perf Mode

P041

P040

Decel Time 1

Autotune

P042

P041

Reset To Defalts

Accel Time 1

P053

P042

Voltage Class

Decel Time 1

P038

A051-A054

Digital In 1-4 Sel

(no such number)

t065-t068, same terminals 05-08

A055

Relay Out Sel

(no such number)

t076, Relay 1. N.C. contact: Relay 2, t081

A065

Analog Out Sel

(no such number)

t088

A103-A107

RS-485 settings

(no such number)

C123-C127, same order

A164

Comm Write Mode

(no such number)

C121

Moving a PowerFlex 40 parameters list to a PowerFlex 525: what each old number turns into.

The classic is P041 = 1. On a PF40 that's a factory reset, on a 525 you just changed Accel Time 1. Option numbers don't carry over either: keypad start is 0 on a PF40 and 1 on a 525, and a 3-wire station that was just P036 = 1 needs P046 = 2, t062 = 49 and t063 = 51.

On the hardware side, the 525 ships with the same 01-11 jumper plus a second one across S1, S2 and S+ for Safe Torque Off, which stays in unless a safety circuit replaces it. It also has 16 presets on four inputs instead of 8 on three. The rest of the 525 setup is in my notes on PowerFlex 525 parameters.

FAQ

How do I reset a PowerFlex 40 to factory defaults?

P041 = 1 "Factory Rset". Clear the F48 that follows, then program. On a 525 the reset is P053.

Why does my PowerFlex 40 run at 5 Hz no matter what the speed reference says?

Most often terminal 05 is closed, and at its default A051 selects preset A071, 5.0 Hz. Open the contact, set A051 to 0 "Not Used", or put the old preset value back.

What's in the PowerFlex 40 parameters list besides P031 to P043?

The read-only d group (frequency, current, fault codes, d012, d016) and the A group: inputs, outputs, presets, Accel/Decel Time 2, comms, PID, StepLogic.

Does a PowerFlex 40 parameters list carry over to a PowerFlex 525?

Not by number. Only P031 to P033 match, so rebuild the 525 by function with the table above.

If the old drive is done

Sometimes the old PF40 isn't coming back. IQElectro has surplus PowerFlex 40 drives like the 22B-D010N104, and the 525 that replaces it, the 25B-D010N104. To get the PowerFlex 40 parameters list off a drive that still powers up there's the 22-HIM-A3 handheld and the 22-HIM-C2S panel HIM, both CopyCat, the 1203-USB converter for a laptop, and the 22-COMM-E if the drive sits on EtherNet/IP. Send us the nameplate photo from step one and we'll match the catalog number against the shelf.