The request usually comes from someone who just moved up from 525s: "can you send me the PowerFlex 755 parameter list?" On a 525 that's a fair question: one table and you're done, and that's exactly the shape my PowerFlex 525 notes take. A 755 doesn't work that way. What you see depends on the option cards plugged into it, the firmware it runs, and the access level set in P301. Two drives with the same catalog number can show you two different lists.
So here is how the list is built, how to get the real one out of the drive in front of you, and the handful of parameters I open first when a 755 won't run.
Why there is no single PowerFlex 755 parameter list
Three things decide what shows up on the screen.
Access level first. P301 [Access Level] has three settings: 0 Basic, 1 Advanced, 2 Expert. Basic is a short operator view. Expert shows the whole drive. When somebody hands me a parameter number and swears it isn't there, P301 is the first thing I check, and more often than not the drive was simply sitting in Basic.
Then ports. A 755 is really a stack of tables. The drive itself is Port 0. Every option card gets its own port, and its parameters start again from 1. "Parameter 1" means nothing until you say which port. Frames 8 to 10 add two more ports for the power hardware.
And firmware. Parameters get added over the years. P990, P991 and P992, the individual U, V and W phase currents, only exist from firmware 20.003. A spare that sat on a shelf for a while will show a shorter PowerFlex 755 parameter list than the drive it's replacing.
|
Port |
What lives there |
What I look at there |
|
0 |
The drive itself: motor data, speed reference, stop modes, status, faults |
P25-P31, P35, P545, P933, P935, P951 |
|
1, 2 |
DPI ports for a HIM or a PC tool |
Their speed references land in Port 0 as P871 and P872 |
|
4 and up |
Option slots: I/O, encoder, communication and safety cards |
Each card's own list, numbered from 1 |
|
10, 11 |
Frames 8 to 10 only: inverter, converter, precharge |
Power-side status and faults |
|
13 |
Embedded EtherNet/IP |
IP address P38-P41, datalinks P1-P32, fault actions |
|
14 |
Embedded DeviceLogix (755 only) |
P53 DLX Operation |
Where parameters live on a PowerFlex 755
Read the label before you read the list
Before I open the PowerFlex 755 parameter list on a drive, I look at two things: the catalog number and the firmware.
The first three characters give you the family. 20F is a PowerFlex 753 (frames 1 to 7), 20G is a PowerFlex 755 (frames 1 to 10), 21G is a 755 with options (frames 8 to 10). The 753 and 755 share most of the numbering, but not all of it. Port 14 DeviceLogix and P877, the reference from the embedded EtherNet/IP port, exist only on the 755.
A classic 755 reads 20G1 at the start. A 20G2 or 20GE number is a TotalFORCE drive, the 755TS and its relatives, and that's a different list altogether. More on that further down.

The first three characters tell you whether the PowerFlex 755 parameter list applies at all.
The HIM will show you the firmware revision and hardware series of the drive and of every peripheral plugged into it, under the DIAGNOSTIC folder, Device Version. The series is also printed as SER on the label. Write both down before you change anything. You'll want them again the day this drive gets replaced.
How to pull the real list out of your drive
The PowerFlex 755 parameter list that actually matters is the one stored in the drive you're standing in front of. Three ways to get it out.
On the HIM. Set P301 to 2 (Expert) first, then go port by port. Port 00 is the drive itself, option cards show up under their own port numbers. Inside a port the parameters are sorted into files and groups. The drive has 11 files and they're the same on every 755: Monitor, Motor Control, Feedback & I/O, Drive Cfg, Protection, Speed Control, Torque Control, Position Control, Communication, Diagnostics and Applications. Once you know which file a function belongs to, you stop scrolling through hundreds of numbers.
In software. Connected Components Workbench and the older DriveExecutive both show the same parameters either as one linear list or grouped by file. My habit: upload the whole drive and save the file before I touch a single value. Takes a couple of minutes and it has saved me more than once.
In Studio 5000. If the drive sits in a Logix project, the drive tab shows the same parameters, but only with the drive Add-On Profile installed. Watch the major firmware revision too. Before drive firmware 16.003 on Series A and 20.003 on Series B, a project built for 14.005 refused a drive running 16.002 over the embedded EtherNet/IP port, even with Compatible Module keying. From those versions on, Compatible Module keying accepts a different major revision.
There's one more copy worth having, on the HIM itself. CopyCat on a 20-HIM-A6 or 20-HIM-C6S can upload all ports of the drive into one file. The HIM holds up to 50 single parameter sets or up to 5 of those all-port files, a bit fewer if you mix the two.
The parameters I check first
This is my working short list, the part of the PowerFlex 755 parameter list I open on almost every service call. Everything below is Port 0, numbered as on firmware up to 20.003.
|
Parameter |
Name |
Why I look at it |
|
P1 |
Output Frequency |
What the drive actually puts out |
|
P2 |
Commanded SpdRef |
What it thinks it was asked for. P2 right and P1 wrong sends me to P945 |
|
P25-P31 |
Motor nameplate data |
Volts, amps, hertz, RPM, power, poles. First thing wrong after a motor swap |
|
P35 |
Motor Ctrl Mode |
0 Induction VHz, 1 Induction SV (default), 3 Induction FV, plus PM and SynRM modes |
|
P155 |
DI Enable |
Which input enables the drive. Default 0.00, nothing assigned |
|
P301 |
Access Level |
0 Basic, 1 Advanced, 2 Expert |
|
P324 |
Logic Mask |
Which ports are allowed to command the drive |
|
P370 |
Stop Mode A |
Ramp (default), Coast, DC Brake and others. Some stop modes ignore the decel time on a stop |
|
P520, P522 |
Max Fwd Speed, Min Fwd Speed |
Min Fwd Speed defaults to 0.00 Hz |
|
P535, P537 |
Accel Time 1, Decel Time 1 |
10.00 s each by default |
|
P545 |
Spd Ref A Sel |
Default 871, the HIM on Port 1. For a PLC on the embedded port, point it at P877 |
|
P571-P577 |
Preset Speed 1-7 |
Defaults follow the motor nameplate hertz and the voltage class |
|
P933 |
Start Inhibits |
Bit by bit, why it won't start |
|
P935 |
Drive Status 1 |
Ready, Active, At Speed, Running, Cur Limit |
|
P945 |
At Limit Status |
Which limit is holding the speed back |
|
P951 |
Last Fault Code |
Where I start after a trip |
PowerFlex 755 parameter list: the first-check parameters (Port 0)
P545 is worth a second look because it's an indirect parameter. It doesn't hold a speed, it holds an address: two digits of port, four digits of parameter number, and the bit after the decimal point. The same format runs through every input assignment. P163 [DI Run] set to 040001.00 means port 4, parameter 1, bit 0, so digital input 0 on the I/O card in port 4. The 871 in P545 points at P871 [Port 1 Reference], which is whatever the HIM on Port 1 sends.

A fresh PowerFlex 755 listens to the HIM for speed until P545 is pointed at P877.
When the drive won't do what you told it
Most of what I'm called out for on a 755 ends up being one of a few entries in the PowerFlex 755 parameter list, not a broken drive.
Say a PLC writes 45 Hz over the embedded EtherNet/IP port and the motor sits at whatever someone last dialed in on the HIM. The drive isn't ignoring the PLC. P545 is still at its default, so the reference comes from Port 1. On the HIM it reads P00 P0871. Change it to Port 00, parameter 877, and the PLC owns the speed.
The other classic: Not Enabled on the display, no fault, no run. Open P933 [Start Inhibits] and read the bits. Bit 2 (Enable) means an enable input is open: either P155 points at an input that's off, or someone pulled the ENABLE jumper on the main control board. With that jumper out, digital input 0 on TB1 becomes a dedicated hardware enable that ignores P155 completely, so with nothing wired to DI0 the drive just sits there. Bit 7 (Safety) points at the safety option instead. A Safe Torque Off card needs 24 V on both SP+ and SE+ before the drive enables. And the SAFETY jumper that ships installed has to come out when that card goes in, or the drive faults the moment it gets a start command.

P933 on a PowerFlex 755: bit 2 and bit 7 explain most "Not Enabled" calls.
The rest of the usual suspects fit in one table.
|
What the drive does |
Check first |
What it usually means |
|
Not Enabled, no fault |
P933 bits 2 and 7, P934 [Last StrtInhibit] |
Enable input off, or the safety option blocking the start |
|
Runs, ignores the PLC speed |
P545, then P2 |
Reference still comes from the HIM (871) instead of P877 |
|
Starts from the HIM, not from the PLC |
P324 [Logic Mask], P933 bit 4 and P919 [Stop Owner] |
That port isn't allowed to command, or something is holding a stop |
|
Commanded speed is right, output is lower |
P945, P935 bits 26 and 27 |
The drive is sitting on a limit, often current limit |
|
Stop takes longer than P537 says |
P370, P371 |
The selected stop mode skips P537 during a stop |
|
A parameter you were told about isn't there |
P301, the port number, the firmware |
Basic view, wrong port, or older firmware |
|
EtherNet/IP connection keeps timing out |
The scanner's firmware |
From drive firmware 9.001 the port needs QoS: 1756-ENBT 4.005 or later, CompactLogix 1769-L2x/L3x 17.03 or later. A 1756-EN2T needs no update |
|
Shows up as an unknown device in Studio 5000 |
Add-On Profile, major firmware revision |
The drive profile isn't installed or doesn't match the drive's major revision |
Symptom first, then the parameter
Before you swap in a spare
Say the dead drive ran 16.x and the shelf spare carries the same catalog number but older firmware. You put the HIM with the old drive's CopyCat file on the new drive and start a download. It stops with a message as soon as it sees a mismatch in firmware revision, device type or series. It also stops if the drive is running or protected by an access code.
You can push on past the warning, but write down which parameters didn't load. Every one of those is yours to set by hand. I'd rather flash the spare to the old drive's firmware first and let CopyCat do the whole PowerFlex 755 parameter list in one go. Check the series as well: the same fixes came out as 16.003 for Series A and 20.003 for Series B. Same story in Studio 5000 when the spare runs firmware older than those: Compatible Module keying on it rejects a project built for a different major revision.
PowerFlex 755TS: same names, new numbers
If the drive is a 755TS, the PowerFlex 755 parameter list you know won't help you with numbers. Parameters moved to a Port:Parameter scheme, a lot of them left Port 0 for Port 10, and some have no equivalent at all. These are the ones I get asked about most.
|
PowerFlex 755 (Port 0) |
PowerFlex 755TS |
Name on the 755TS |
|
P25 Motor NP Volts |
10:400 |
Motor NP Volts |
|
P28 Motor NP RPM |
10:403 |
Motor NP RPM |
|
P35 Motor Ctrl Mode |
0:65 |
Pri MtrCtrl Mode |
|
P301 Access Level |
0:30 |
Access Level |
|
P324 Logic Mask |
0:41 |
Logic Mask |
|
P370 Stop Mode A |
10:110 |
Mtr Stop Mode A |
|
P535 Accel Time 1 |
10:1915 |
VRef Accel Time1 |
|
P537 Decel Time 1 |
10:1917 |
VRef Decel Time1 |
|
P545 Spd Ref A Sel |
10:1800 |
VRef A Sel |
|
P571-P577 Preset Speed 1-7 |
10:1814-10:1820 |
Preset Speed 1-7 |
|
P895-P902, P905-P912 Data In/Out (DPI datalinks) |
Not supported |
No equivalent |
PowerFlex 755 vs 755TS: where common parameters moved
Even the values shift. Induction SV is 1 in P35 on a 755 and 2 in 0:65 on a 755TS. Induction FV goes from 3 to 4. Adjustable voltage mode, 9 on a 755, doesn't exist on the TS at all. Copy a setting across by number and you'll land on the wrong motor control mode, so I treat an old 755 file as a checklist, never as something to download.
FAQ
Is there one PowerFlex 755 parameter list for every drive?
No. Port 0 is the same base on every 755, but each option card adds a port with its own parameters, newer firmware adds parameters, and P301 in Basic hides everything outside a short operator set. The list you need is the one uploaded from your drive.
Where can I see the PowerFlex 755 parameter list for my own drive?
On the drive itself. Set P301 to 2 (Expert) on the HIM and go port by port, or upload the drive into Connected Components Workbench or the Studio 5000 drive tab and save the file.
Does a PowerFlex 755 parameter list work on a 755TS?
Names mostly carry over. Numbers don't. A 755TS uses Port:Parameter numbering (Accel Time 1 is 10:1915, not P535), and some enumerations changed too, motor control mode included.
Why can't I find a parameter on the HIM?
Usually P301 is set to Basic or Advanced and the parameter belongs to a higher level. The other two causes: you're in the wrong port, or the parameter was added in a later firmware than the one loaded.
If the drive itself is the problem
Sometimes the PowerFlex 755 parameter list checks out line by line and the drive still won't run. Then it's hardware. Before ordering anything, write down the catalog number and series off the old label, and the firmware off the HIM. IQElectro lists PowerFlex 755 drives across several sizes, such as the 22 A 20G11ND022JA0NNNNN, the 40 A 20G11ND040AA0NNNNN and the 248 A 20G1AND248JN0NNNNN, along with the 20-HIM-C6S remote HIM and the 20-750-S Safe Torque Off card. Every one comes with a 2-year warranty. Check the spare's series and firmware against the old drive before it goes in, and CopyCat will do the rest.